9
|
Electrical installation
Installer reference guide
94
Item
Heat pump convector
Remote outdoor sensor
Remote indoor sensor
Description
There are different controllers and setups
possible for the heat pump convectors.
Depending on the setup, you also need to
implement a relay (field supply, see
addendum book for optional equipment).
For more information, see:
Installation manual of the heat pump
convectors
Installation manual of the heat pump
convector options
Addendum book for optional equipment
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
[2.9] Control
[2.A] Ext thermostat type
For the additional zone:
[3.A] Ext thermostat type
[3.9] (read-only) Control
See:
Installation manual of the remote outdoor
sensor
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (External sensor = Outdoor)
[9.B.2] Ext. amb. sensor offset
[9.B.3] Averaging time
See:
Installation manual of the remote indoor
sensor
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (External sensor = Room)
[1.7] Room sensor offset
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05