Installation manual
Daikin Altherma 3 M
https://daikintechnicaldatahub.eu
EBLA04E2V3
EBLA06E2V3
EBLA08E2V3
EBLA04E23V3
EBLA06E23V3
EBLA08E23V3
EDLA04E2V3
EDLA06E2V3
EDLA08E2V3
EDLA04E23V3
Installation manual
EDLA06E23V3
English
Daikin Altherma 3 M
EDLA08E23V3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EBLA08E23V3 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin EBLA08E23V3

  • Page 1 Installation manual Daikin Altherma 3 M https://daikintechnicaldatahub.eu EBLA04E2V3 EBLA06E2V3 EBLA08E2V3 EBLA04E23V3 EBLA06E23V3 EBLA08E23V3 EDLA04E2V3 EDLA06E2V3 EDLA08E2V3 EDLA04E23V3 Installation manual EDLA06E23V3 English Daikin Altherma 3 M EDLA08E23V3...
  • Page 2 3P685234-1C...
  • Page 3 3P685234-1C...
  • Page 4 3P685234-3D...
  • Page 5 3P685234-3D...
  • Page 6: Table Of Contents

    Configuration wizard: System ........31 Latest revisions of the supplied documentation may be available on 8.2.4 Configuration wizard: Backup heater ......33 the regional Daikin website or via your dealer. 8.2.5 Configuration wizard: Main zone......... 33 8.2.6 Configuration wizard: Additional zone......34...
  • Page 7: Specific Installer Safety Instructions

    Daikin website (publicly accessible). Mounting the outdoor unit (see "4.2 Mounting the outdoor unit" [ 4  9]) ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). WARNING Online tools Fixing method of the outdoor unit MUST be in accordance In addition to the documentation set, some online tools are available with the instructions from this manual.
  • Page 8: About The Box

    User interface (front plate, rear plate, screws, and wall plugs) 3-way valve 10 m Unit mounting plate (a), (b) (25 m Vibration dampers Cable tie external backup heater kit 10 m Bolts, nuts, washers, and spring washers Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 9: Additional Installation Site Requirements Of The Outdoor Unit In Cold Climates

    Heating Solutions Navigator which can be reached via unit" [ 4  9] for more details. outdoor https://professional.standbyme.daikin.eu. Please contact your In heavy snowfall areas it is very important to select an installation dealer if you have no access to Heating Solutions Navigator.
  • Page 10: To Install The Outdoor Unit

    2 Place the 2 cables over the outdoor unit. 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint (field supply). Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 11: Opening And Closing The Unit

    To have easier front access, rotate the switch box out of the unit as follows: Prerequisite: The front plate has been removed. 1 Push down the clip of the switch box holder. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 12: Piping Installation

    In case the minimum flow rate cannot be reached, (*) Maximum temperature for piping and accessories a flow error 7H will be generated (no heating or operation). See the installer reference guide for more information. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 13: Third-Party Tank Requirements

    The unit contains an automatic air purge valve. Make sure it is open. All automatic air purge valves in the system (in the unit, and in the field piping – if any) must remain open after commissioning. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 14: To Protect The Water Circuit Against Freezing

    About freeze protection valves When no glycol is added to the water, you can use freeze protection valves to drain the water from the system before it can freeze. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 15: To Fill The Domestic Hot Water Tank

    Do NOT push or place redundant cable length in the unit. Smart Grid "6.3.14 To connect a Smart Grid" [ 4  27]. NOTICE The distance between the high voltage and low voltage cables should be at least 50 mm. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 16 See: Interface ▪ Installation and operation manual of the Human Comfort Interface ▪ Addendum book optional equipment Wires: 2×(0.75~1.25 mm²) Maximum length: 500 m [2.9] Control [1.6] Room sensor offset Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 17: To Connect The Electrical Wiring To The Outdoor Unit

    The following illustration shows the location of the extra components ▪ In case of preferential kWh rate power supply that you need to install on the outdoor unit when using certain option kits. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 18 [9.8] Benefit kWh power supply 1 Access the electrical connections. See "6.3.1  To connect the unit" [ 4  17]. electrical wiring to the outdoor 2 Connect the preferential kWh rate power supply. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 19: To Connect The Backup Heater Power Supply

    X19A X11YA X11Y X11YB 3 Fix the cable with cable ties to the cable tie mountings. 6 Fix the cables with cable ties to the cable tie mountings. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 20: External Backup Heater Kit

    52.9Ω 52.9Ω 52.9Ω 52.9Ω for F1B. K1M/5 K2M/1 ∞ 132.3Ω ∞ ∞ 2 If required, modify the connection on terminal X14M. Example measure resistance between K1M/1 and K5M/13: Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 21 2 On the outdoor unit, connect the HV cable to the appropriate terminals as shown in the illustration below. 6 7 8 9 10 X15M EKLBUHCB6W EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 22: To Connect The User Interface

    ▪ Connecting the user interface cable to the outdoor unit. ▪ Installing the user interface, and connecting the user interface cable to it. ▪ (if necessary) Opening the user interface after it is installed. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 23 ▪ Choose one of the 4 possible wiring intakes (a, b, c or d). ▪ If you choose the left or right side, make a hole for the cable in the part of the casing where the casing is thinner. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 24: To Connect The Shut-Off Valve

    2 Push the rear plate on each of the 4 spots where the snap-fits are located. 3 Fix the cable with cable ties to the cable tie mountings. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 25: To Connect The Electricity Meters

    4  17]. electrical wiring to the outdoor A4P.Y1 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below. X2M.7 EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 26: To Connect The Space Cooling/Heating On/Off Output

    2 Connect the changeover to external heat source cable to the Wire between X2M and A4P appropriate terminals as shown in the illustration below. A4P Installation of EKRP1HBAA is required. A4P.X1 A4P.X2 A4P.Y2 X2M.7 Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 27: To Connect The Power Consumption Digital Inputs

    ▪ In case of low voltage Smart Grid contacts ▪ In case of high voltage Smart Grid contacts. This requires the installation of the Smart Grid relay kit (EKRELSG). EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 28 Relay for Smart Grid contact 2 X10M Terminal block Screws for X10M Screws for K1A and K2A Sticker to put on the high voltage wires Wires between the relays and X5M (AWG22 ORG) Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 29: Finishing The Outdoor Unit Installation

    This chapter describes what you have to do and know to configure the system after it is installed. NOTICE This chapter explains only the basic configuration. For more detailed explanation and background information, see the installer reference guide. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 30: To Access The Most Used Commands

    Installer pin code The Installer pin code is 5678. Additional menu items and installer settings are now available. 6 Press the left dial to confirm the new setting. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 31: Configuration Wizard

    ▪ When Emergency is set to Automatic and a heat pump failure occurs, the backup heater automatically takes over the heat load, and the booster heater in the optional tank takes over the domestic hot water production. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 32 Code Description [E-0D] Glycol Filled system: Is the system filled with glycol? ▪ 0: No ▪ 1: Yes a Main LWT zone Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 33: Configuration Wizard: Backup Heater

    Maximum 60°C Fixed 8°C INFORMATION Settings [9.3.3] and [9.3.5] are linked. Changing one setting influences the other. If you change one, check if the other is still as expected. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 34: Configuration Wizard: Additional Zone

    Influence of the LWT setpoint mode [2.4] is as follows: ▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving water temperatures, either preset or custom. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 35: Weather-Dependent Curve

    The weather-dependent curve is available for: tank temperature. It is the desired temperature when a storage ▪ Main zone - Heating economic action is scheduled (preferably during day). EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 36: 2-Points Curve

    For example, if leaving water temperature is in general fine but at low ambient temperatures too cold, raise the slope so that leaving water temperature is heated increasingly more at decreasingly lower ambient temperatures. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 37: Using Weather-Dependent Curves

    ON/OFF setpoints for that zone or for the tank. When the maximum condition. or minimum setpoint is reached, the curve flattens out. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 38: Additional Zone

    ▪ 2: 2 contacts 8.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 39: Menu Structure: Overview Installer Settings

    Averaging time [9.C] Bivalent Bivalent Boiler efficiency Temperature Hysteresis Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 40: Commissioning

    There are NO damaged components or squeezed commissioning instructions in this chapter, a general pipes on the inside of the outdoor unit. commissioning checklist is also available on the Daikin Business Portal (authentication required). Only for models with integrated backup heater (F1B: field...
  • Page 41: To Perform An Air Purge

    Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off Space heating/cooling and Tank operation. 1 Set the user permission level to Installer. See "To — level" [ 4  30]. change the user permission EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 42: 10 Hand-Over To The User

    ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 43: 11 Technical Data

    11 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 11.1 Piping diagram: Outdoor unit...
  • Page 44 Heating Muffler with filter Cooling Distributor Heat exchanger Connections: 4‑way valve Screw connection Accumulator Flare connection Compressor Quick coupling Muffler Brazed connection Gas stop valve with service port Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 45: Wiring Diagram: Outdoor Unit

    Field wiring terminal for AC RTH2 Resistor External backup heater terminal Connector Booster heater power supply S1PH High pressure switch terminal S2~80 Connector Field wiring terminal for DC EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 46 * External indoor or outdoor NO valve Normal open valve ambient thermistor Only for LAN adapter Only for LAN adapter * Flow switch Optional for *** Optional for *** Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 47 Switch box (3) BUH switch box (3) Backup heater switch box Rear Rear (4) Legend (4) Legend *: Optional; #: Field supply Main PCB * Digital I/O PCB EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Installation manual Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 48 A8P: X801M: 3-5 4 core Optional part for EWA*/EWYA* signal X5M: 15-16 A11P: X1B: 1-2 2 core Power limitation demand input 4 A8P: X801M: 4-5 signal 4D139354 A Installation manual EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3 Daikin Altherma 3 M 4P685229-1D – 2022.10...
  • Page 52 4P685229-1D 2022.10 Verantwortung für Energie und Umwelt...