To check the water volume ........8.2.2 Quick wizard: Standard ..........6.3.4 Changing the pre-pressure of the expansion vessel . 8.2.3 Quick wizard: Options ..........Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
To pump down ................74 13.2 To start and stop forced cooling ..........75 Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer. 14 Glossary ............. 75 15 Technical data ........... 76 15.1 Dimensions and service space ..........
(as indicated on the nameplate of the unit). ▪ Do NOT touch any accidental leaking refrigerant. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ When installing the earth leakage protector, make sure it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Indoor unit 3.2.1 To unpack the indoor unit 2 Tilt the bottom side of the front panel upwards and remove it. 3 Remove the accessories. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
For installation instructions, see the installation manual of the drain pan. Drain pan heater (EKDPH008CA) The drain pan heater is required to avoid freezing-up of the drain pan. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
The domestic hot water tank can be connected to the indoor unit for For installation instructions, see the installation manual of the digital providing domestic hot water. I/O PCB and addendum book for optional equipment. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
(optional equipment EKRUCAL) installed in the room and used questions first: as room thermostat ▪ How many rooms are heated (or cooled) by the Daikin heat pump system? ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C –...
Page 10
Benefits ▪ Highest comfort and efficiency. The smart room thermostat ▪ Wireless. The Daikin external room thermostat is available in a functionality can decrease or increase the desired leaving water wireless version. temperature based on the actual room temperature (modulation).
Mind situations where the main room can be heated by is decided by the external ▪ #: [A.2.1.7] another heating source. Example: Fireplaces. thermostat. ▪ Code: [C-07] ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
(X2M/1 and X2M/4). The indoor unit will only supply leaving water temperature when there is an actual demand. INFORMATION To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump convector.
INFORMATION A Additional leaving water temperature zone B Room 1 To increase comfort and performance, Daikin recommends C Room 2 to install the valve kit option EKVKHPC on each heat pump D Main leaving water temperature zone convector.
▪ Depending on the demand, the indoor unit supplies different leaving water temperature matching the design temperature of the different heat emitters. ▪ Under floor heating has the best performance with Altherma LT. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split...
Page 15
▪ Make sure the auxiliary boiler and its integration in the Only for EHBH/X system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Make sure the return water to the heat pump does NOT exceed 55°C.
55°C (50°C if outdoor temperature is low). The electrical resistance integrated in the heat pump can higher this temperature. However, this consumes more energy. Daikin recommends to set the desired DHW tank temperature below 55°C to avoid using the electrical resistance.
▪ If energy prices are the same during the day and the night, water, see "8 Configuration" on page 42. Daikin recommends to heat up the DHW tank during the day. ▪ Connecting the electrical wiring of the standalone DHW tank to ▪...
One power meter that covers the entire system is sufficient. 5.5.1 Produced heat ▪ Applicable for all models. Setup Connect the power meter to X5M/7 and X5M/8. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ The power limitation level can be activated: 5.5.4 Preferential kWh rate power supply ▪ Permanently ▪ By digital inputs General rule ▪ Power meter 1: Measures the outdoor unit. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
The outdoor unit has better efficiency than the electrical heaters. Therefore, the electrical heaters are limited and turned OFF first. The power or current of the entire Daikin system is limited The system limits power consumption in the following order: dynamically by digital inputs (maximum four steps).
Backup heater. ▪ That is NOT exposed to direct sunlight Result: The booster heater will ▪ If this is NOT possible, Daikin recommends to connect a remote be turned OFF first. outdoor sensor (option EKRSCA1). ▪ Setup: For installation instructions, see the installation manual of Turns OFF all electrical heaters.
▪ Mind the following spacing installation guidelines: Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
The minimal pipe thickness for R410A piping must be Deformation of the piping can cause malfunctioning of the unit. in accordance with the following table. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ The installation must be in compliance with the applicable b Indoor unit legislation and may require additional hygienic installation c Heat exchanger measures. d Backup heater e Pump Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder valve of the expansion vessel. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
The following illustration is an example and may NOT b Backup heater match your system layout. c Indoor unit d Domestic hot water tank e Booster heater Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
More technical specifications of the different connections are indicated on: ▪ Wiring diagram in the switch box of the unit ▪ "15.6 Wiring diagram" on page 84 ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
On this pedestal it is then recommended to install the EKFT008CA option kit to guarantee the minimum space of 10 cm below the bottom plate of the unit. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
NOTICE The pedestal MUST be aligned with the backside of the a Drain pan U‑beam. b U-beams 3 Remove the protective cardboard and instruction sheet. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Do NOT grasp the piping to lift the indoor unit. inserted screws. 1 Lift the unit from the package. 6 Hook the unit against the wall. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ Do NOT reuse piping from previous installations. ▪ NEVER install a drier to this R410A unit to guarantee its lifetime. The drying material may dissolve and damage the system. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ Set the nitrogen pressure to 20 kPa (just enough so it can be felt on the skin) with a pressure-reducing valve. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
2 Check for leaks by applying the bubble test solution to all connections. a Liquid stop valve 3 Discharge all nitrogen gas. b Gas stop valve c Service port ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
If the total liquid piping length Then… is… ≤10 m Do NOT add additional refrigerant. >10 m Add 20 g refrigerant per extra meter (above 10 m). Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
6 Close the drain and fill valve. 7 Disconnect the water supply hose from the drain and fill valve. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Curled single core wire b Screw c Flat washer Stranded conductor wire with round crimp- style terminal a Terminal b Screw c Flat washer Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
NOT come in contact with the piping and sharp edges. CAUTION Do NOT push or place redundant cable length in the unit. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
NEVER use a power circuit shared by another appliance. This power circuit must be protected with the required safety devices according to the applicable legislation. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
2 Fix the wallplate of the user interface to the frontplate of the 230 V 230 V 230 V 400 V 400 V unit. K1M/1 K5M/13 52.9Ω 52.9Ω 52.9Ω ∞ ∞ K1M/3 ∞ ∞ ∞ 105.8Ω 105.8Ω ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
7.6.7 To connect the shut-off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Installation of EKRP1HB is required. 2 Fix the cable with cable ties to the cable tie mountings. 2 Fix the cable with cable ties to the cable tie mountings. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
"8.5 Menu structure: Overview installer settings" on page 67. For access to the setting codes, see "To access the installer settings" on page 43. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
3 If you do NOT press any button for more than 1 hour or press interfaces. again for more than 4 seconds, the user permission level switches back to End user. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Cancel Confirm Adjust 5 The user interface re-initialises and you can proceed the installation by setting the other applicable settings and commissioning of the system. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 45
▪ a: Add LWT zone ▪ b: Main LWT zone ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ 2 (Request): Pump operation based on request. Example: Using a room thermostat creates thermo ON/OFF condition. When there is no such demand, the pump is OFF. Remark: Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 47
(X2M/1 and 2). "5 Application guidelines" on page 9. Select this value in case of connection with the wired (EKRTWA) or wireless (EKRTR1) room thermostat. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
5°C. See the user reference guide and/or operation manual for more details about this function. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 49
[1-02] as for high outdoor Remark: This value can only be temperatures less warm water is set in leaving water temperature required. control. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 50
5°C~22°C set in leaving water temperature (default: 18°C). control. Note: This value should be lower than [1-08] as for high outdoor temperatures colder water required. Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 51
1°C; default value: 5°C). [A.3.1.3.2] [9-0A] Cooling: required temperature difference between entering and leaving water. Range: 3~10°C (in steps of 1°C; default value: 5°C). ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
[A.4.3.2.1] 1 person and how the unit acts upon it. The absolute desired tank temperature for 1 person. 30~80°C (default: 42°C) Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
8.2.7 Contact/helpdesk number Code Description [6.3.2] Number that users can call in case of problems. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 55
Only applicable in case of room thermostat control. The hysteresis this setting to: band around the desired room temperature is settable. Daikin advises NOT to change the room temperature hysteresis as it is set ▪ avoid leaving water supply to the heat emitters in the main LWT for an optimal use of the system.
Note that the ▪ storage economic outdoor temperature will be time-averaged (see "8 Configuration" ▪ storage comfort on page 42). Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 57
In reheat mode, desired tank temperature weather dependent. Note: When displayed tank temperature is weather dependent, it cannot be adjusted on the user interface. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 58
ON and booster always taken into account. heater OFF temperature. The minimum Range: 5~95 minutes (default: 30) hysteresis temperature is 2°C. Range: 2~40°C (default: 2) Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
In this way it is possible to limit the backup heater capacity. [5-00] Is backup heater operation allowed above equilibrium temperature during space heating operation? ▪ 1: NOT allowed ▪ 0: Allowed Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 61
— based on the outdoor temperature — which heating this temperature, bivalent heat source can/will provide the space heating, either the Daikin indoor source permission signal will be active. unit or an auxiliary boiler. [C-04] Hysteresis. The field setting "bivalent operation" apply only the indoor unit space Temperature difference between bivalent heating operation and the permission signal for the auxiliary boiler.
(because the function reapplies the remote controller settings at the time of the heat exchanger coil is not operational) power failure. Therefore, Daikin recommends to always enable the with a warmer top layer. function. Range: 0~20°C (default: 10).
Page 63
Defines whether the outdoor unit power supply can be interrupted (internally by indoor unit control) during stand-still conditions (no space heating/cooling nor domestic hot water demand). The final ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 64
The outdoor temperature is averaged over the selected time period. Code Description [A.6.4] [1-0A] Outdoor average timer: ▪ No averaging (default) ▪ 12 hours ▪ 24 hours ▪ 48 hours ▪ 72 hours Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 65
This functionality is only valid in specific conditions where it is preferable to keep the pump active when <4°C (pump will be activated for 10 minutes and disactivated after 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality. Code...
Amp. value [A.7] Commissioning kW value Test run Amp. limits for DI kW limits for DI UFH screed dryout Air purge Priority Actuator test run ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Installer settings > Commissioning > Air purge > Circuit. There is NO water leak inside the indoor unit. 8 Select the desired circuit and press Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
(heating/cooling mode) and tank temperature (domestic hot water mode). For monitoring the temperature, go to [A.6] and select the information you want to check. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Maintenance should preferably be carried out yearly by an Desired LWT 25°C installer or service agent. Stop 9.6.3 To readout the status of an underfloor heating screed dryout 1 Press Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
▪ Water flow coming from the relief valve is high enough, no blockage of the valve or in between piping is suspected. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
25). minimum required value (see "6.3.3 To check the water volume" on page 24). Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
This chapter gives you an overview of all error codes and the content of the error code as it appears on the user interface. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Please contact your dealer. 13.1 To pump down Abnormal increase tank temperature. In order to protect the environment, be sure to pump down in following cases: Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
To start and stop forced cooling the accompanying documentation. Confirm that dipswitch SW2 is in COOL mode. Field supply 1 Press the forced cooling operation switch SW1 to begin forced Equipment not made by Daikin that can be combined with cooling. product according instructions accompanying documentation.
SHUT OFF VALVE WITH DRAIN/FILL VALVE (1-1/4˝ F BSP) (INCLUDED ACCESSORY) WATER FILTER POWER SUPPLY/COMMUNICATION WIRE ENTRANCE SERVICE DOOR SWITCHBOX TERMINALS SWITCHBOX TERMINALS FOR DOMESTIC HOT WATER TANK (OPTION) 3D078463 ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
15 Technical data 15.2 Center of gravity 15.2.1 Center of gravity: Outdoor unit UNIT 4TW60819-1 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
The fuse is blown when the temperature becomes higher than the backup heater thermal protector temperature. s Backup heater thermal protector The protector activates when the temperature of the backup heater becomes too high. ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Main PCB A1P s Socket X9A, receives the thermistor connector. (Only for installations with domestic hot water tank) t PCB fuse FU1 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
On/OFF thermostat (wired) (*) : standard for *HV*, optional for *HB* # : field supply On/OFF thermostat (wireless) Ext. thermistor Heat pump convector 4D077028 page 1 ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 88
Only for demand PCB option only for EKBPHT* only if no EKBPHT* Options: bottom plate heater OR On/OFF output Only for digital I/O PCB option 4D077028 page 3 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 89
* = Optional Relay on PCB (*) = Standard for EHVH/X, optional for EHBH/X Main supply pump # = Field supply Domestic hot water pump Black ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
In case user interface is relocated 2x0.75 X5M: 1-2 A2P: P1-P2 user interface communication Only for *KRCAL* OPTIONAL PART 2 core 2x0.75 communication A2P: P1-P2 user interface 4D078494 ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 92
Regular kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced Benefit kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced 4D078288 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 94
(2) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. 3TW60811-1 B page 2 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 95
(1) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current max. running current >16A and ≤75A per phase. (2) : See figure A 3TW60811-1 B page 3 ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
(11) BUH 3V/9W can only operate at flow > 12/15 l/min (12) Refer to operation range for differences between RHQ* and RLQ* units (13) DB/WB 7°C/6°C - LWC 45°C ( DT=5°C) 3D078754_D page 1 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Page 97
(**) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤75A per phase. 3D078754_D page 2 (***) : System impedance ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
In case such conditions ara expected, the *RLQ must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. 3TW60813-1A Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
–20 domestic hot water domestic hot water –25 –25 tank temperature (°C) tank temperature (°C) 40 45 55 60 40 45 INDOOR UNITS: CA-SERIES 3TW60813-2B ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered. 4D078990 Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Power input is total input of indoor and outdoor unit, inclusive the circulation pump; according to standard EN 14511 Notes: - The capacity and power input is valid for V3-models at 230V. - The capacity and power input is at maximum operation 3TW60812-1A ERLQ004~008CAV3 + EHBH/X04+08CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
See also minimum and maximum allowed waterflow range in the technical specifications. 2) Water quality must be according to EN directive EC 98/83 EC. 4D078649_A Installer reference guide ERLQ004~008CAV3 + EHBH/X04+08CA Daikin Altherma - Low Temperature Split 4P313774-1C – 2012.11...
Need help?