Application guidelines
Heat pump convectors – Multiple rooms
Installer reference guide
40
▪
The user interface connected to the outdoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the outdoor unit.
▪
The room thermostats are connected to the shut-off valves. They are also
connected to the outdoor unit (X2M/35 and X2M/30) -via a relay (field supplied)-
to give feedback when operation is needed. The outdoor unit will supply leaving
water as soon as there is a request from one of the rooms.
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
External room thermostat for the main
zone:
▪
#: [2.A]
▪
Code: [C-05]
Benefits
Compared with radiators for one room:
▪
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a User interface (delivered as accessory)
b Heat pump convectors (+ controllers)
▪
For more information about connecting the electrical wiring to the unit, see
"9.2 Connections to the outdoor
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
B
C
A
a
b
b
4
unit" [
91].
Value
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05