11
|
Configuration
Installer reference guide
152
If...
▪
Space heating/cooling=On, and
▪
The external room thermostat is
"Thermo OFF", and
▪
Outdoor temperature drops below
6°C
▪
Space heating/cooling=On, and
▪
The external room thermostat is
"Thermo ON"
In case of 2 leaving water temperature zones:
If...
▪
Space
heating/cooling=Off,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
Space heating/cooling=On, and
▪
Operation mode=Heating, and
▪
The external room thermostat is
"Thermo OFF", and
▪
Outdoor temperature drops below
6°C
▪
Space heating/cooling=On, and
▪
Operation mode=Cooling
Room thermostat control ([C‑07]=2)
During room thermostat control, room frost protection [2‑06] is guaranteed when
activated. If so, and the room temperature drops below the room antifrost
temperature [2‑05], the unit will supply leaving water to the heat emitters to heat
up the room again.
#
Code
[1.4.1]
[2-06]
[1.4.2]
[2-05]
INFORMATION
When the dedicated Human Comfort Interface (BRC1HHDA used as room
thermostat) is disconnected (because of incorrect wiring or damage of the cable),
then room frost protection is NOT guaranteed.
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
Room frost protection is guaranteed by
the normal logic.
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
There is no room frost protection.
Description
Activation:
▪
0 No: Antifrost functionality is OFF.
▪
1 Yes: Antifrost functionality is on.
Room setpoint:
▪
4°C~16°C
Then...
Then...
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05