Daikin EBLA09D V3 Series Installer's Reference Manual page 202

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

11
|
Configuration
Water pipe freeze prevention
Installer reference guide
202
#
Code
[9.6.5]
[8-00]
[9.6.6]
[8-01]
[9.6.7]
[8-04]
Only relevant for installations with water piping outdoors. This function tries to
protect outdoor water piping from freezing.
#
Code
[9.7]
[4-04]
NOTICE
If the system does NOT contain a backup heater, then:
Make sure that the room antifrost control is activated ([2-06]=1).
Do NOT change the default room antifrost temperature [2-05].
Make sure that the water pipe freeze prevention is activated ([4-04]≠2).
NOTICE
Water pipe freeze prevention. Even if you turn OFF space heating/cooling operation
([C.2]: Operation > Space heating/cooling), water pipe freeze prevention –if
enabled– will remain active.
Description
Minimum running timer:
Do NOT change.
Maximum running timer for domestic hot
water operation. Domestic hot water heating
stops even when the target domestic hot water
temperature is NOT reached. The actual
maximum running time also depends on setting
[8-04].
When Control=Room
preset value is only taken into account if there
is a request for space heating or cooling. If
there is NO request for space heating/cooling,
the tank is heated until the setpoint has been
reached.
When Control≠Room
preset value is always taken into account.
Range: 5~95 minutes
Remark: It is NOT allowed to set [8‑01] to a value
below 10 minutes.
Additional timer: Additional running time
for the maximum running time depending on the
outdoor temperature [4-02] or [F-01].
Range: 0~95 minutes
Description
Water pipe freeze prevention:
0: Continuous pump operation. Do NOT
use.
1: Non continuous pump operation
2: Off
thermostat: This
thermostat: This
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05