EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
Capacity – Power
supply
3 kW 1N~ 230 V
6 kW 1N~ 230 V
6 kW 3N~ 400 V
9 kW 3N~ 400 V
3 Fix the cable with cable ties to the cable tie mountings.
During connection of the backup heater, miswiring is possible. To detect possible
miswiring, it is highly recommended to measure the resistance value of the heater
elements. Depending on the capacity and power supply, following resistance
values (see table below) should be measured. ALWAYS measure the resistance on
the contactor clamps K1M, K2M, and K5M.
K1M/1
K5M/13
K1M/3
K1M/5
K1M/3
K1M/5
F1B
F1B
L
L
N
N
Q3DI
L
N
1N~ , 50 Hz
230 V AC
F1B
L1 L2
L3
N
Q3DI
L1
L2
L3
N
3N~ , 50 Hz
400 V AC
3 kW
6 kW
1N~ 230 V
1N~ 230 V
52.9Ω
52.9Ω
105.8Ω
158.7Ω
26.5Ω
52.9Ω
9
Electrical installation
|
X14M
X14M
1 2 3 4 5 6
X14M
1 2 3 4 5 6
6 kW
9 kW
3N~ 400 V
3N~ 400 V
105.8Ω
105.8Ω
105.8Ω
105.8Ω
105.8Ω
105.8Ω
Installer reference guide
103