Daikin EBLA09D V3 Series Installer's Reference Manual page 214

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

11
|
Configuration
Alarm output
Auto restart
Installer reference guide
214
Alarm output
#
Code
[9.D]
[C–09]
Alarm output logic
[C-09]
0
Closed output
1
Open output
Auto restart
When power returns after a power supply failure, the auto restart function
reapplies the user interface settings at the time of the power failure. Therefore, it
is recommended to always enable the function.
If the preferential kWh rate power supply is of the type that power supply is
interrupted, always enable the auto restart function. Continuous hydro module
control can be guaranteed independent of the preferential kWh rate power supply
status, by connecting the hydro module to a separate normal kWh rate power
supply.
#
Code
[9.E]
[3-00]
Alarm output: Indicates the logic of alarm
output on digital I/O PCB during high level indoor
unit error malfunctioning. Low level errors
(caution/warning) will NOT be transmitted to
alarm output.
0 Abnormal: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
1 Normal: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).
Alarm
No alarm
Open output
Closed output
Auto restart:
0: Manual
1: Automatic
Description
No power supply
to unit
Open output
Description
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05

Advertisement

Table of Contents
loading

Table of Contents