Code
[9.5.2]
[7-06]
Glycol Filled system
This setting gives the installer the possibility to indicate whether the system is filled
with glycol or water. This is important in case glycol is used to protect the water
circuit against freezing. If NOT set correctly, the liquid in the piping can freeze.
#
Code
N/A
[E-0D]
NOTICE
If you add glycol to the water, you also need to install a flow switch (EKFLSW1).
Priorities
For systems with a separate domestic hot water tank.
#
[9.6.1]
[5-02]
[9.6.2]
[5-03]
Activation of the Compressor forced off
mode:
0: disabled
1: enabled
Glycol Filled system: Is the system filled
with glycol?
0: No
1: Yes
Code
Space heating priority: Defines
whether domestic hot water is made by
booster heater only when outdoor
temperature is below space heating priority
temperature.
0: Off (default)
1: On
Please do NOT change the default value.
[5-01] Equilibrium temperature and [5-03]
Space heating priority temperature are related
to backup heater. So, you must set [5-03] equal
or a few degrees higher than [5-01].
Priority temperature: Defines the
outdoor temperature which below the
domestic hot water will be heated by booster
heater only.
Please do NOT change the default value.
Range: –15°C~35°C
Description
Description
Description
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05