To Connect A Smart Grid - Daikin EBLA09D V3 Series Installer's Reference Manual

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

9
|
Electrical installation

9.2.14 To connect a Smart Grid

Installer reference guide
118
This topic describes 2 possible ways to connect the outdoor unit to a Smart Grid:
In case of low voltage Smart Grid contacts
In case of high voltage Smart Grid contacts. This requires the installation of the
Smart Grid relay kit (EKRELSG).
The 2 incoming Smart Grid contacts can activate the following Smart Grid modes:
Smart Grid contact
1
0
0
1
1
The use of a Smart Grid pulse meter is not mandatory:
If Smart Grid pulse meter is...
Used
([9.A.2] Electricity meter 2 ≠
None)
Not used
([9.A.2] Electricity meter 2 =
None)
In case of low voltage Smart Grid contacts
Wires (Smart Grid pulse meter): 0.5 mm²
Wires (low voltage Smart Grid contacts): 0.5 mm²
[9.8.4]=3 (Benefit kWh power supply = Smart grid)
[9.8.5] Smart grid operation mode
[9.8.6] Allow electrical heaters
[9.8.7] Enable room buffering
[9.8.8] Limit setting kW
The wiring of the Smart Grid in case of low voltage contacts is as follows:
X5M
3
4
5
6
9
10
2
1
S4S
S11S
S10S
a Jumper (factory-mounted). If you also connect a safety thermostat (Q4L), replace
the jumper with the safety thermostat wires.
S4S Smart Grid pulse meter (optional)
1
/S10S Low voltage Smart Grid contact 1
2
/S11S Low voltage Smart Grid contact 2
1 Open the service cover. See
2 Connect the wiring as follows:
2
0
Free running
1
Forced off
0
Recommended on
1
Forced on
Then [9.8.8] Limit setting kW is...
Not applicable
Applicable
13
14
a
"7.3.2 To open the outdoor
Smart Grid operation mode
4
unit" [
 72].
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05

Advertisement

Table of Contents
loading

Table of Contents