Daikin EBLA09D V3 Series Installer's Reference Manual page 156

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

11
|
Configuration
Installer reference guide
156
#
Code
[2.5]
[1-00]
[1-01]
[1-02]
[1-03]
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4]=2):
Description
Set weather-dependent heating:
Note: There are 2 methods to set the weather
dependent curve. See
"11.5.2 2-points
4
curve" [
 144] and
"11.5.3 Slope-offset
4
curve" [
 145]. Both curve types require 4 field
settings to be configured according to the figure
below.
T t
[1-02]
[1-03]
[1-00]
[1-01]
T
: Target leaving water temperature (main
t
zone)
T
: Outdoor temperature
a
[1-00]: Low outdoor ambient temperature. –
40°C~+5°C
[1-01]: High outdoor ambient temperature.
10°C~25°C
[1-02]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑01]°C~[9‑00]°C
Note: This value should be higher than [1‑03]
as for low outdoor temperatures warmer water
is required.
[1-03]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑01]°C~min(45, [9‑00])°C
Note: This value should be lower than [1‑02] as
for high outdoor temperatures less warm water
is required.
T a
ambient
temperature.
ambient
temperature.
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05