Daikin EBLA09D V3 Series Installer's Reference Manual page 203

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

Benefit kWh power supply
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
NOTICE
ONLY disable water pipe freeze prevention if glycol is used. For more information on
freeze protection by glycol, see
4
freezing" [
 82].
#
Code
[9.8.2]
[D-00]
[9.8.3]
[D-05]
"8.2.4  To protect the water circuit against
Description
Restriction: Only applicable if [9.8.4] is NOT set
to Smart grid.
Allow heater: Which heaters are allowed to
operate during preferential kWh rate power
supply?
0 No: None
1 Only BSH: Booster heater only
2 Only BUH: Backup heater only
3 All: All heaters
See also below table (Allowed heaters during
preferential kWh rate power supply).
Setting 2 is only meaningful if the preferential
kWh rate power supply is of type 1 or the hydro
module is connected to a separate normal kWh
rate power supply (via X2M/5‑6) and the backup
heater is NOT connected to the preferential kWh
rate power supply.
Restriction: Only applicable if [9.8.4] is NOT set
to Smart grid.
Allow pump:
0 No: Pump is forced off
1 Yes: No limitation
11
Configuration
|
Installer reference guide
203