Application guidelines
Installer reference guide
46
Bivalent operation is only possible if
-
Space heating is turned ON, and
-
DHW tank operation is turned OFF.
Domestic hot water is always produced by the DHW tank connected to the
outdoor unit.
INFORMATION
During heating operation of the heat pump, the heat pump operates to achieve
the desired temperature set via the user interface. When weather-dependent
operation is active, the water temperature is determined automatically
depending on the outdoor temperature.
During heating operation of the auxiliary boiler, the auxiliary boiler operates to
achieve the desired water temperature set via the auxiliary boiler controller.
Setup
Integrate the auxiliary boiler as follows:
A
A Main leaving water temperature zone
B One single room
a User interface (delivered as accessory)
b Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
c Non-return valve (field supply)
d Shut-off valve (field supply)
e Auxiliary boiler (field supply)
f Aquastat valve (field supply)
NOTICE
Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
Make sure the return water to the heat pump does NOT exceed 60°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
-
Install an aquastat valve in the return water flow of the heat  pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
Install non-return valves.
B
f
d
e
d
c
c
a
b
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05