Heat pump convectors
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
Setup
A Main leaving water temperature zone
B One single room
a User interface (delivered as accessory)
b Heat pump convectors (+ controllers)
▪
For more information about connecting the electrical wiring to the unit, see
"9.2 Connections to the outdoor
▪
The heat pump convectors are directly connected to the outdoor unit – or to the
external backup heater kit, if there is one.
▪
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment
▪
The space heating/cooling demand signal is sent to one digital input on the
outdoor unit (X2M/35 and X2M/30).
▪
The space operation mode is sent to the heat pump convectors by one digital
output on the outdoor unit (X2M/4 and X2M/3).
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
External room thermostat for the main
zone:
▪
#: [2.A]
▪
Code: [C-05]
Benefits
▪
Cooling. The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
▪
Efficiency. Optimal energy efficiency because of the interlink function.
B
A
b
a
4
unit" [
91].
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
6
Application guidelines
|
Value
Installer reference guide
35