Radiators – Multiple external room thermostats
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
The user interface connected to the outdoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the outdoor unit.
The room thermostats are connected to the shut-off valves, and do NOT have to
be connected to the outdoor unit. The outdoor unit will supply leaving water all
the time, with the possibility to program a leaving water schedule.
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
Benefits
Compared with underfloor heating for one room:
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Setup
a
A Main leaving water temperature zone
B Room 1
C Room 2
a User interface (delivered as accessory)
b External room thermostat
c Bypass valve
d Relay
For more information about connecting the electrical wiring to the unit, see
"9.2 Connections to the outdoor
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum
water flow as described in table "To check the water volume and flow rate" in
"8.1 Preparing water
piping" [
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
0 (Single zone): Main
B
C
A
M1
d
b
4
unit" [
 91].
4
 73].
6
Application guidelines
|
Value
c
M2
b
Installer reference guide
39