Daikin EBLA09D V3 Series Installer's Reference Manual page 277

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

Field settings table
Breadcrumb Field code
Setting name
9.I
[7-05]
Boiler efficiency
9.I
[7-06]
Compressor forced off
9.I
[7-07]
BBR16 activation
9.I
[8-00]
Minimum running time for domestic hot water operation.
9.I
[8-01]
Maximum running time for domestic hot water operation.
9.I
[8-02]
Anti-recycling time.
9.I
[8-03]
Booster heater delay timer.
9.I
[8-04]
Additional running time for the maximum running time.
9.I
[8-05]
Allow modulation of the LWT to control the room temp?
9.I
[8-06]
Leaving water temperature maximum modulation.
9.I
[8-07]
What is the desired comfort main LWT in cooling?
9.I
[8-08]
What is the desired eco main LWT in cooling?
9.I
[8-09]
What is the desired comfort main LWT in heating?
9.I
[8-0A]
What is the desired eco main LWT in heating?
9.I
[8-0B]
--
9.I
[8-0C]
--
9.I
[8-0D]
--
9.I
[9-00]
What is the maximum desired LWT for main zone in heating?
9.I
[9-01]
What is the mimimum desired LWT for main zone in heating?
9.I
[9-02]
What is the maximum desired LWT for main zone in cooling?
9.I
[9-03]
What is the mimimum desired LWT for main zone in cooling?
9.I
[9-04]
Leaving water temperature overshoot temperature.
9.I
[9-05]
What is the mimimum desired LWT for add. zone in heating?
9.I
[9-06]
What is the maximum desired LWT for add. zone in heating?
9.I
[9-07]
What is the mimimum desired LWT for add. zone in cooling?
9.I
[9-08]
What is the maximum desired LWT for add. zone in cooling?
9.I
[9-09]
What is the allowed undershoot in cooling?
9.I
[9-0A]
What is the room buffering temperature in heating?
9.I
[9-0B]
What is the room buffering temperature in Cooling?
9.I
[9-0C]
Room temperature hysteresis.
9.I
[9-0D]
Pump speed limitation
9.I
[9-0E]
--
9.I
[C-00]
Domestic heating water priority.
9.I
[C-01]
--
9.I
[C-02]
Is an external backup heat source connected?
9.I
[C-03]
Bivalent activation temperature.
9.I
[C-04]
Bivalent hysteresis temperature.
9.I
[C-05]
What is the thermo request contact type for the main zone?
9.I
[C-06]
What is the thermo request contact type for the add. zone?
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
--
9.I
[C-0C]
--
9.I
[C-0D]
--
9.I
[C-0E]
--
(*1) *V3/W1*
(*2) *3V3/3W1*
(*3) EDLA*
(*4) EBLA*
Range, step
Default value
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/O
0~20 min, step 1 min
1 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~10 hour, step: 0,5 hour
3 hour
R/W
20~95 min, step: 5 min
50 min
R/W
0~95 min, step: 5 min
95 min
R/W
0: No
1: Yes
R/W
0~10°C, step: 1°C
5°C
R/W
[9-03]~[9-02], step: 1°C
18°C
R/W
[9-03]~[9-02], step: 1°C
20°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~[9-00], step: 1°C
33°C
13
10
16
R/W
[2-0C]=2:
37~60, step: 1°C
60°C
[2-0C]≠2:
37~55, step: 1°C
55°C
R/W
15~37°C, step: 1°C
25°C
R/W
18~22°C, step: 1°C
22°C
R/W
5~18°C, step: 1°C
7°C
R/W
1~4°C, step: 1°C
4°C
R/W
15~37°C, step: 1°C
25°C
R/W
[2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]≠2:
37~55, step: 1°C
55°C
R/W
5~18°C, step: 1°C
7°C
R/W
18~22°C, step: 1°C
22°C
R/W
1~18°C, step: 1°C
18°C
R/W
[3-07]~[3-06]°C, step: 0,5°C
23°C
R/W
[3-09]~[3-08]°C, step: 0,5°C
23°C
R/W
1~6°C, step: 0,5°C
1 °C
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6
6
R/W
0: Solar priority
1: Heat pump priority
0
R/W
0: No
1: Bivalent
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
0: -
1: 1 contact
2: 2 contacts
R/W
0: -
1: 1 contact
2: 2 contacts
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
0: Normally open
1: Normally closed
0
0
0
0
0
9/11
Installer setting at variance with
default value
Date
Value
4P627273-1B - 2022.05