11-4 Troubleshooting
Alarm No. 99.0
Alarm No. 99.0 may occur due to the timing between safety input 1/2 and alarm clear input.
This alarm will occur if both of the following conditions are met:
 An alarm was cleared when at least one of the input photocouplers for safety inputs 1 and 2 was
OFF (which means that a Safety Input Error (Alarm No. 30.0) had occurred).
 At least one of the input photocouplers for safety inputs 1 and 2 was turned from OFF to ON in a
specific period during the alarm clear process (See below).
Safety input 1
Safety input 2
Alarm reset
input (RESET)
*1. Alarm No. 99.0 will occur if at least one of the input photocouplers for safety inputs 1 and 2 is turned
Be sure to clear the alarm after turning ON the photocouplers for safety inputs 1 and 2 again.
11
11-27
Approx. 120 ms
Alarm
Alarm No. 30.0
occurred
from OFF to ON.
Precautions for Correct Use
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
*1
Specified period
Approx. 1 ms
Alarm No. 99.0