The following safety precautions must be followed whenever any type of voltage or
Safety
precautions
current connection is being made to the 4400.
• Wear proper Personal Protective Equipment, including safety glasses and insulated
gloves when making connections to power circuits.
• Hands, shoes and floor must be dry when making any connection to a power line.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
• Press the 4400 On/Off power button to Off.
• Before connecting to electric circuits to be monitored, open their related circuit
breakers or disconnects. DO NOT install any connection of the 4400 to live power
lines.
• Connections must be made to the 4400 first, then connect to the circuit to be
monitored.
CH 2/ Voltage Measurement Cable and Current Probe Connections
Continued on next page
2-3