Verifying Voltage and Current Connections, continued
Phasor displays that show incorrect current probe connection can be corrected by
Incorrect
current phasor
reconnecting the probe so that the arrow on the probe handle points toward the load.
diagram
The 4400 is able to display diagrams of the various wiring configurations to assist users
in the selection of circuit type appropriate for their application (see Chapter 5 Start
Menu - Circuit Type Selection on page 5-11). The instrument compares the detected
voltages, currents, and phase sequence (if applicable) to the selected circuit type. The
4400 issues a message if the specified circuit type and the actual voltage/current
connections match.
The next pages describe and illustrate the wiring configurations available for set up in
4400.
Interconnect Jumpers bearing part number 114013-G1 supplied with the standard cable
WARNING
set can be used to bond the same conductor points together. To reduce the risk of fire,
electric shock, or physical injury, it is strongly recommended that connections be made
with all circuits de-energized and current carrying conductors fused. If it is necessary to
make connections on energized circuits, these must be performed by Qualified
Personnel ONLY with Proper Personal Protective Equipment.