Parameter Settings in Each Monitoring Mode
The following table lists the default settings for the threshold parameters in each
Setup
parameters
monitoring mode.
Parameters
High Limit
Low Limit
Very Low
Limit
RMS Pre-
trigger (cycles)
RMS In-Out
Post-trigger
(cycles)
RMS Out-In
Post-trigger
(cycles)
Waveform
Capture Pre-
trigger (cycles)
Waveform
Capture Post-
trigger (cycles)
Absolute
Instantaneous
Peak
Cycle-by-cycle
Waveshape
Magnitude
Cycle-by-cycle
Waveshape
Duration (% of
cycle)
Waveform
Duration
Standard
Current
Power
Inrush
Recorder
Quality
RMS Variation
110%
120%
90%
Off
10%
Off
6
4
6
200
6
200
2
4
2
200
Transients
170%
350%
10%
Off
10%
Off
7%
Off
APPENDIX B/ Technical Specifications
Fault
Long-term
Timed
Recording
110%
Off
90%
Off
10%
Off
4
0
100
10 (50 Hz);
12 (60 Hz)
1000
10 (50 Hz);
12 (60 Hz)
4
0
1000
10 (50 Hz);
12 (60 Hz)
170%
Off
10%
Off
10%
Off
7%
Off
Continuous
EN50160
Data
Logging
Off
110%
Off
90%
Off
1%
1
6
2
6
2
6
1
2
2
2
Off
170%
Off
10%
Off
10%
Off
7%
Continued on next page
B-9
Need help?
Do you have a question about the DBPGFLEX3KPKG and is the answer not in the manual?