Terminal
Text
58
CAN L (Reserved)
59
CAN H (Reserved)
60
Reserved
61
Reserved

4.4 Typical wiring diagram

Figure 4.1
SGC 410 typical wiring
P1
L1
s1
L2
G
L3
N
P2
s2
P1
s1
43
Supply
1
-
NOTE
Wiring diagrams are examples. Use the application's wiring diagram during installation.
Genset and mains contactor latching relays should be compiled against 4 kV surge as per IEC-61000-4-5 standard.
Relay cards used with the controller should be protected against reverse battery voltages.
Analogue input 2 used for Fuel level sensor can be wired with the reference to Battery Negative, see Specifications,
Analogue resistive sensor inputs.
Communication ports for CAN ( terminals 58 and 59) and RS-485 (terminals 31 and 32) have built-in 120 Ω termination
resistors.
If a digital output is connected to a relay, the relay must include freewheeling diodes.
USER MANUAL 4189341243A UK
P2
s2
P1
P2
s1
s2
P1
P2
s1
s2
42 45 44 47 46 49
48
54 55 56 57
AC voltage
AC current CT
genset
Outputs
2
3
4
5
6
7
8
9
10
F1
+
B+
G
+
+
Description
CAN Low
CAN High
-
-
GB
F4
33 34 35 36 37 38 39 40 41
Digital inputs (configurable)
Analogue inputs
11 12 13
16
14 15 21
D+
Engine
body
Connector
BCP-508-4GN
BTS
battery
22
24 25
L1
L2
L3
N
50 51 52 53
CAN
RS485
ECU
31 32
58 59
Page 17 of 78