9.2

Test Suite Integrated in the Device

Test Functions

9.2.1
After you complete the initial startup (see chapter
grated in the device. To do this, establish connection to the online device. In the project tree, open the Folder
Test Suite. Underneath you will find the individual test points that are explained to you in the following chap-
ters. The following figure shows the project tree.
[scproans-110413-01.tif, 1, en_US]
Figure 9-1
If you have activated a connection password for the device, you must enter it in the corresponding dialog.
After correct password entry, the connection between DIGSI 5 and device is established. In case of wrong
entry, the connection is not established.
If you have configured a confirmation ID with DIGSI 5, this is queried when you access the individual test func-
tions. Enter here the corresponding 6-digit number.
You will find details for configuring the password and the confirmation ID in chapter
Connection Password, and Confirmation ID During Operation
If the connection between DIGSI 5 and the device is interrupted during a test function, re-establish the
connection to the device. Then do a reset on the device with DIGSI 5. If no connection can be established,
then do the reset directly on the device through the on-site operation panel. After successful reset, the device
is now in a normal operating state
NOTE
i
i
The device must be set in another mode for most tests. If the tests occur in a system in operation, ensure
that the running operation is interrupted.
After successful tests, bring the device back to the previous mode in the following manner:
Confirm the link Show device mode in the upper right of the work window.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018
Project Tree
9.3.3 Initializing Device and Verifying Basic
9.2 Test Suite Integrated in the Device
9.3 Initial
Startup), you can access the test functions inte-
of this manual.
Commissioning
11.6 Authentication,
Status.
191

Advertisement

Table of Contents
loading

Table of Contents