Siemens SIPROTEC 5 V7.80 Operation page 59

Table of Contents

Advertisement

Type of Line
Stranded wires with bootlace ferrules
or pin-type lugs
Solid conductor, bare (2 mm
NOTE
i
i
Make sure that the cables and lines of extra-low voltage circuits are laid sufficiently far away from power
network circuits.
Torques for Other Screw Types
Screw Type
M4 x 20
M4 x 8
M2.5 x 6
Countersunk screw, M2.5 x 6
Countersunk screw, M2.5 x 8
Collar screw, M4 x 20
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018
3.3 Surface-Mounted Devices with Detached On-Site Operation Panel
Current
Voltage Terminal with
Terminal
Spring-Loaded Terminals
2.7 Nm
1.0 Nm
2.0 Nm
1.0 Nm
2
)
Torque
1.2 Nm
1.2 Nm
0.39 Nm
0.39 Nm
0.39 Nm
0.7 Nm
Fitting the Devices
Voltage Terminal with
Screw Connection
0.6 Nm