Operation in the Operating State
8.4 Indications
Acknowledgment of Stored Indications
8.4.8
Acknowledgment on the On-Site Operation Panel
Acknowledgment via LED Reset key
Operating the key first causes the activation of all LEDs (LED test) when pressed, and when released, the reset-
ting of all stored indications. Stored LEDs, output contacts, and spontaneous fault displays are reset.
Acknowledgment via the operating menu
•
In order to reach the reset functions from the main menu, use the navigation buttons of the on-site
operation panel.
•
On the device display, select:
Main menu → Device functions → Reset functions
You are offered different reset options.
Figure 8-11
Detailed overview of the reset functions:
Res. Binary Outputs
•
Use Res. binary outputs to reset stored output contacts.
•
Actuate the softkey Start in the base bar.
•
If necessary, enter the confirmation ID on request.
•
Confirm with the softkey Enter.
Do not reset LEDs in FG
•
Use Do not reset LEDs in FG to reset stored LEDs that are not assigned to a special function group.
•
Actuate the softkey Start in the base bar.
•
If necessary, enter the confirmation ID on request.
•
Confirm with the softkey Enter.
Depending on the device configuration, other protection function groups are displayed to you as submenus
for which separately corresponding, stored LEDs can be reset. Proceed with the other function groups as
shown in the following example.
Line 1 (example)
•
Go to the submenu of the selected function group (example Line 1).
•
Use Reset LEDs to reset stored LEDs in the selected function group.
•
Actuate the softkey Start in the base bar.
•
If necessary, enter the confirmation ID on request.
•
Confirm with the softkey Enter.
Figure 8-12
134
Reset Functions on the On-Site Operation Panel (Example)
Reset Functions on the On-Site Operation Panel (for Example, Line FG)