Download Print this page
Siemens 599-01134 Technical Instructions
Siemens 599-01134 Technical Instructions

Siemens 599-01134 Technical Instructions

Mz series zone control three-way valves

Advertisement

Quick Links

Powermite 599 Series
MZ Series Zone Control
Three-way Valves
Description
Features
Application
Product Numbers
The Powermite 599 Series ANSI Class 250 MZ Series three-way valves are designed to
work the SSB MZ Series actuator with a 7/32-inch (5.5 mm) stroke.
Direct coupled universal bonnet
ANSI Leakage Class IV (0.01% of Cv)
A typical application for the Powermite three-way valve is the mixing of hot or chilled
water for convectors, fan coil units, unit conditioners, radiation, reheat coils, and similar
terminal units requiring an actuator that delivers a minimum of 45 pounds force (200 N).
Table 1. Product Numbers.
Flow Rate
Line Size
Cv
(Kvs)
inch
(mm)
0.4
(0.34)
1/2
0.63 (0.54)
1/2
1
(0.85)
1/2
1.6
(1.37)
1/2
2.5
(2.15)
1/2
4
(3.44)
1/2
6.3
(5.43)
3/4
10
(8.6)
1
Technical Instructions
Document No. 155-199P25
Product
Number
(15)
599-01132
(15)
599-01133
(15)
599-01134
(15)
599-01135
(15)
599-01136
(15)
599-01137
(20)
599-01138
(25)
599-01139
VF 599-8
October 24, 2005
Siemens Industry, Inc.

Advertisement

loading

Summary of Contents for Siemens 599-01134

  • Page 1 Table 1. Product Numbers. Product Numbers Flow Rate Line Size Product (Kvs) inch (mm) Number (0.34) (15) 599-01132 0.63 (0.54) (15) 599-01133 (0.85) (15) 599-01134 (1.37) (15) 599-01135 (2.15) (15) 599-01136 (3.44) (15) 599-01137 (5.43) (20) 599-01138 (8.6) (25) 599-01139 Siemens Industry, Inc.
  • Page 2 NEMA 1 (interior only) Dimensions See Tables 6 and 7 and Figures 4 and 5 Valve Weight See Table 6 Service Kit Protective black knob 4 268 8895 0 to cover the bonnet and threads Page 2 Siemens Industry, Inc.
  • Page 3 0.14 0.43 0.61 0.75 0.87 0.97 1.06 1.23 1.37 1.7 0.21 0.68 0.96 1.17 1.35 1.51 1.66 1.91 2.15 2.6 0.34 1.1 0.54 1.7 9.4 10.9 12.1 0.86 2.7 8.6 10.5 12.2 14.9 17.2 19.2 Siemens Industry, Inc. Page 3...
  • Page 4 30 (207) 1/2", 0.4< Cv <1.6 25 (172) (15 mm, 0.34< Kvs <1.37) 1/2", 2.5< Cv <4 15 (103) Bottom port (15 mm, 2.15< Kvs <3.44) 3/4" and 1" (20 mm and 25 mm) 10 (69) Page 4 Siemens Industry, Inc.
  • Page 5 • The medium to be controlled: water, etc. • The maximum inlet temperature and pressure of the medium at the valve. • The pressure differential that will exist across the valve under maximum load demand. Siemens Industry, Inc. Page 5...
  • Page 6 (mm) lb (kg) 2-3/4 2-15/16 1-5/16 1.10 (15) (70) (74) (33) (0.5) 3-1/4 3-9/16 1-5/16 1.44 (20) (83) (90) (33) (.65) 3-7/8 3-15/16 1-9/16 2.20 (25) (98) (99) (39) (1.0) Figure 4. Three-way Valve. Page 6 Siemens Industry, Inc.
  • Page 7 Actuator Width Code Actuator, H1 1/2 (15) 4-7/8 (124) 13-1/8 (330) 3-1/4 (83) 11-1/4 (282) 3/4 (20) 4-7/8 (124) 13-1/8 (330) 3-1/4 (83) 11-1/4 (282) 1 (25) 5-1/8 (130) 13-3/8 (335) 3-1/4 (83) 11-1/4 (282) Siemens Industry, Inc. Page 7...
  • Page 8 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2005 Siemens Industry, Inc. Your feedback is important to us. If you have Document No.

This manual is also suitable for:

599-01133Powermite 599 series599-01132599-01136599-01137599-01135 ... Show all