Operation in the Operating State
8.9 Control System on Site
[scklndis-090413-01.tif, 1, en_US]
Figure 8-65
8.9.7

Acquisition Blocking and Manual Updating

During commissioning, maintenance, or testing, a brief interruption of the connection between the logical
signals and binary inputs may be useful. It allows you to manually update the status of a switching device that
is not providing feedback correctly. Before this can take place, you must first set acquisition blocking.
To set the acquisition blocking, proceed as follows:
Using the navigation keys, move in the main menu of the device display to
Commands→Equipment→Aq.blkman. update.
Select the appropriate device (for example, a circuit breaker) from among the several switching devices
using the navigation keys.
Press the Change softkey.
Enter the confirmation ID (not relevant for active role-based access control (RBAC) in the device).
Confirm the process with the softkey marked OK in the display.
After entering the confirmation ID (only with the RBAC inactive), acquisition blocking is switched on.
[scerfass-310816-01, 1, en_US]
Figure 8-66
Manual updating of the switching device is possible from within the same menu.
Select Manual update
Select the switching device setting to be updated manually using the navigation keys (for example, off,
Figure
8-68).
Confirm the process with the softkey marked OK in the display.
184
Control from the List on the Small Display
Activating Acquisition Blocking
(Figure
8-67) using the navigation keys.