Manual defrost

Triggering defrost

Resetting limitations

Definition of responsibilities

Output test relays

Siemens Switzerland Ltd
HVAC Products
Line no.
Operating line
7152
Triggering defrost
No ¦ Yes
The heat pump's defrost function can be manually triggered via this operating line.
Line no.
Operating line
7160
Reset limitation
No
Yes
If, due to the "Min off time" or the "Limitation source temp min", the heat pump is
switched off, it can be put back into operation via parameter "Reset limitation".
Line no.
Operating line
7181
Phone no. responsibility 1
7183
Phone no. responsibility 2
These operating lines are used to set the phone numbers for the relevant error and
maintenance messages.

6.22 Input / output test

The input / output test is used to check correct functioning of the connected
components.
When selecting a setting from the relay test, the relevant relay is energized, thus
putting the connected component into operation. The correct functioning of the relays
and correct wiring can thus be tested.
Line no.
Operating line
7700
Relay test
No test
Everything off
Source pump Q8/Ventilat K19
Compressor K1 (for approx. 1 - 2 s)
Condenser pump Q9
DHW pump Q3
Heating circuit pump Q2
Heating circ mix valve op Y1
Heat circ mix valve cl Y2
Relay output QX23 module 1
Relay output QX21 module 1
Relay output QX22 module 1
Relay output QX1 (for approx. 1- 2 s)
Relay output QX2
Relay output QX3
Relay output QX4
Relay output QX5
Relay output QX6
Relay output QX23 module 2
Relay output QX21 module 2
Relay output QX22 module 2
Important:
During the relay test, limitations are not active.
User manual RVS61.843
6 The settings in detail
177/221
CE1U2355en_02
23. November 2007