Saving And Deleting The Logs - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

Operation in the Operating State
8.5 Logs
Configurability
The motor-starting log is only present in the Motor function group. There is no column for the motor-starting
log in the DIGSI information routing. The entries in the motor-starting log are preconfigured and cannot be
changed.
8.5.12

Saving and Deleting the Logs

Deleting the logs of the device in the operating state is unnecessary. If storage capacity is no longer sufficient
for new indications, the oldest indications are automatically overwritten with new incoming events. In order
for the memory to contain information about the new faults in the future, for example, after an inspection of
the system, a deletion of the log makes sense. Resetting the logs is done separately for the various logs.
NOTE
i
i
Before you delete the content of a log on your SIPROTEC 5 device, save the log with DIGSI 5 on the hard
disk drive of your PC.
NOTE
i
i
Not all logs of your SIPROTEC 5 device can be deleted. These limitations apply especially to logs with rele-
vance for security and after-sales (security log, device-diagnosis log, setting-history log).
NOTE
i
i
Upon deletion of the fault log, the associated fault records are also deleted. In addition, the meters for fault
number and fault-record number are reset to 0. In contrast, if you delete fault records, the content of the
fault log, including the allocated fault numbers, remains.
NOTE
i
i
If the device executes an initial start, for example, after an update of the device software, the following
logs are automatically deleted:
Operational log
Fault log
Ground-fault log
Setting-history log
User log
Motor-startup log
Back up the deletable logs using DIGSI 5.
NOTE
i
i
If a ground fault is currently active, the ground-fault log cannot be deleted.
Deleting Logs on the On-Site Operation Panel
To reach the selected log from the main menu, use the navigation keys of the on-site operation panel
(example operational log):
Main Menu → Indications → Operational log
152
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018

Advertisement

Table of Contents
loading

Table of Contents