Setting Time Keeping Parameters - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

Operation in the Operating State
8.8 Change Device Settings
[scdttime-080413-01.tif, 1, en_US]
Figure 8-44
From the Date format menu item, select a display option.
To change the format, press the Change softkey.
Enter the change and then confirm the entry by selecting the Ok softkey.
The Date and Time menu items show you the current values with ongoing update.
To change Date or Time, select the desired menu item and press the Change softkey.
Enter the changes and then confirm the entry by selecting the Ok softkey.

Setting Time Keeping Parameters

8.8.3
Input the time keeping settings of your SIPROTEC 5 device preferably using DIGSI 5. You have access here to
all possible settings. You can only access some of the settings using the on-site operation panel while the
device is being operated.
Settings Using the DIGSI 5
To reach the time settings of your SIPROTEC 5 device, use the project-tree window.
Select
Project → Device → Parameter → Time settings
Select the desired date format.
Configure up to 2 external timers (time source, latency, time zone) and the time by which failures should
be logged.
First decide whether your PC settings should be accepted or whether you wish to enter the settings manually.
Enter the settings for your local time zone and daylight saving time. The settings include the local time
zone (relative to GMT) as well as the daylight saving time options (activation, start, end, and offset of
daylight saving time).
You will find application and setting information in the System Functions Device manual.
168
Date and Time Setting
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018