Confirmation Id - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

11.4

Confirmation ID

NOTE
i
i
If you have not activated access protection with a confirmation code and connection password, the device
operates using role-based access control (see chapter
The confirmation ID consists of 6 digits, see
safety-critical actions, the query also protects against undesirable actions during operation. Use only DIGSI 5 to
set the confirmation IDs. After initialization of the confirmation ID with DIGSI 5, the query is saved in the
device.
Change the confirmation ID as follows.
Double-click the Security menu item in the project tree.
Click the Change... button in the action column (see
Enter the confirmation ID twice.
Confirm the process with OK or cancel it.
All entries are hidden by asterisks.
[scbstcod-021116-01, 1, en_US]
Figure 11-2
Confirmation ID for the Local/Remote Switching Authority
Set the confirmation ID for the switching authority with DIGSI 5. During operation, there is no dialog in DIGSI 5
for this setting. You can change the local or remote switching authority solely via the on-site operation panel.
To change the switching authority, use DIGSI 5 to enter the confirmation ID that you have to enter at the on-
site operation panel.
Enter the setting with the code (local or remote position) for devices with a key switch. There is no query at
the on-site operation panel for devices with a key switch. For devices without a key switch, set the local or
remote position status in the device using a parameter. Changing this parameter requires the entry of the
confirmation ID. If the local position has been set, you cannot execute any switching operations via a substa-
tion control protocol or with DIGSI 5.
Confirmation ID for Non-Interlocked Switching (Interlocking Off)
NOTE
i
i
This is a very critical operation.
Enter the setting of the confirmation ID with DIGSI 5. For devices with a key switch, non-interlocked switching
is possible by selecting the Interlocking Off position. If no key switch is present, there is a confirmation ID in
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018
Changing the Confirmation ID with DIGSI 5
11.9 Operational Security and Access
Table
8-10. If DIGSI 5 is online with the device and you execute
Figure
11-3).
Security Settings in the Device
11.4 Confirmation ID
Control).
243