Siemens SIPROTEC 5 V7.80 Operation page 39

Table of Contents

Advertisement

[dw_first and second device row, 1, en_US]
Figure 3-11
Siemens recommends a drilling space of at least 55 mm (2.17 in) between the 1st and 2nd device row. Due to
the connecting-cable length, the maximum space may be approx. 80 mm (3.15 in). The length of the cable is
890 mm (35.04 in) from the center of the plug to the center of the plug.
[dw_angle rail, 1, en_US]
Figure 3-12
Table 3-1
1/3 device (base module)
1/2 device (base module with one expansion module) 221
2/3 device (base module with 2 expansion modules)
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018
Drilling Pattern – 1/1 Devices, 1st and 2nd Device Row
Angle Rail for Connection of the 1st and 2nd Device Row
Cut-Out Widths
Width of the Assembly Opening in mm (in Inches)
146
+2
mm (5.75
+0.08
)
+2
mm (8.7
+0.08
)
296
+2
mm (11.65
+0.08
)
Fitting the Devices
3.1 Flush-Mounting Devices
39

Advertisement

Table of Contents
loading

Table of Contents