Communication Log - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

Operation in the Operating State
8.5 Logs
NOTE
i
i
The device-diagnosis log cannot be deleted!
The logged indications are preconfigured and cannot be changed!

Communication Log

8.5.9
The logging of the respective status such as ensuing faults, test and diagnosis operation, and communication
capacity utilizations is done for all hardware-based configured communication interfaces. Up to 500 indica-
tions can be stored in the communication log. Logging occurs separately for each communication port of the
configured communication modules.
Reading from the PC with DIGSI 5
Use the project-tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → Device → Test suite → Communication module
Then select:
J:Onboard Ethernet → Communication log
The communication log is shown to you in the state last loaded from the device.
Before this, refresh the contents by clicking the update arrows in the headline.
[sccompuf-140912-01, 2, en_US]
Figure 8-29
Reading on the Device through the On-Site Operation Panel
To reach the communication log from the main menu, use the navigation keys on the on-site operation
panel.
Main Menu → Test & Diagnosis → Log → Communication log
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
148
Reading the Communication Log with DIGSI 5
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018