Special Features When Handling Protocols; Upgrading The Configuration Version - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

[scfwdvlo-280716-01, 1, en_US]
Figure 10-14
After the firmware update of the device and the communication modules, all firmware components of the
device have been updated.
You can find more information on this in

Special Features when Handling Protocols

10.4.3
The firmware for the communication modules consists of the basic firmware and all available protocols. The
communication drivers depend on the device firmware and must be updated together with this firmware.
When you set parameters for a protocol in DIGSI 5 and when you load the configuration into the device, the
protocol firmware is loaded automatically in the device if necessary.

Upgrading the Configuration Version

10.4.4
To be able to use the extended functionality after a firmware update, you must perform an upgrade of the
configuration. Proceed as follows:
NOTE
i
i
Before doing an update, back up the configuration of your SIPROTEC 5 device using DIGSI 5 via Connect to
device and retrieve data!
Start DIGSI 5 on your PC.
Select the device in the project tree.
Open the context menu.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018
Status of Firmware Update
Structure of the HW/SW Information Menu Item, Page
Maintenance, On-the-Spot Assistance and Test
10.4 Update Firmware and Configuration
217.
229