The device remains in commissioning mode until you set the device in the process mode consciously or
until the internal monitoring time (statement of time) has expired. You reach the process mode by clicking
the link in the upper right of the working area. The settings sheet Device information opens. Go to Device
mode to set the device in process mode.
You can execute more tests in this mode.

Creating Signals for Communication Interfaces

9.2.4
The test editor serves to set signals or states in the device that are then output via the communication inter-
faces.

Testing Switching Devices

9.2.5
During a primary test the device in combination with DIGSI 5 offers the possibility of checking switching
devices. Click again the Test button and open the Control functions menu item. The existing switching
devices appear in the operating range. You can set the switching state and read in the status again. To do this,
activate the respective switching device and execute the desired actions. The spontaneous indications log the
behavior of the switching device (see
closing disconnectors or grounding switches. This takes place via the binary feedbacks on the device. Induce
unauthorized circuit states and check whether the interlocking logic stored in a CFC plan works correctly in the
device.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018
Testing a Protection Function (Example, Overvoltage Protection)
Figure
9-6). You can verify the interlocking conditions by opening or
Commissioning
9.2 Test Suite Integrated in the Device
195