Factory Settings Restoration - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Basic functions
Parameter
Values (Range)
Pulse length
10...3600000
Description
Operation mode
0=Pulsed
1=Toggle/Persis-
tent
-1=Off
Pulse length
10...3600000
Description
Operation mode
0=Pulsed
1=Toggle/Persis-
tent
-1=Off
Pulse length
10...3600000
Description
Operation mode
0=Pulsed
1=Toggle/Persis-
tent
-1=Off
Pulse length
10...3600000
Description
Operation mode
0=Pulsed
1=Toggle/Persis-
tent
-1=Off
Pulse length
10...3600000
Description
3.14

Factory settings restoration

In case of configuration data loss or any other file system error that prevents
the merging unit from working properly, the whole file system can be restored to
the original factory state. All default settings and configuration files stored in the
factory are restored. For further information on restoring factory settings, see the
operation manual.
124
Unit
Step
ms
10
ms
10
ms
10
ms
10
ms
10
1MRS758407 C
Default
Description
1000
Pulse length for
pulsed operation
mode
SPCGAPC1 Output
Generic control
12
point description
-1=Off
Operation mode
for generic control
point
1000
Pulse length for
pulsed operation
mode
SPCGAPC1 Output
Generic control
13
point description
-1=Off
Operation mode
for generic control
point
1000
Pulse length for
pulsed operation
mode
SPCGAPC1 Output
Generic control
14
point description
-1=Off
Operation mode
for generic control
point
1000
Pulse length for
pulsed operation
mode
SPCGAPC1 Output
Generic control
15
point description
-1=Off
Operation mode
for generic control
point
1000
Pulse length for
pulsed operation
mode
SPCGAPC1 Output
Generic control
16
point description
Technical Manual
SMU615