Single-Pole Power Output Relays; High-Speed Output Hso With Bio0007 - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Technical data
Description
11.9

Single-pole power output relays

Table 299: Single-pole power output relays
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit
time constant L/R<40 ms, at 48/110/220 V
DC
Minimum contact load
11.10

High-speed output HSO with BIO0007

Table 300: High-speed output HSO with BIO0007
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit
time constant L/R <40 ms, at 48/110/220 V
DC
Operate time
Reset
260
Current drain through the supervision cir-
cuit
Minimum voltage over the TCS contact
Value
~1.5 mA
20 V AC/DC (15...20 V)
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
Value
250 V AC/DC
6 A
15 A
30 A
5 A/3 A/1 A
<1 ms
<20 ms, resistive load
1MRS758407 C
SMU615
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents