Binary Input Settings; Binary Signals In Card Location Xnnn - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

1MRS758407 C
Parameter
Remote override
Remote viewer
Remote operator
Remote engineer
Remote administrator
Local viewer
Local operator
Local engineer
Local administrator
3.1.5

Binary input settings

Table 9: Binary input settings
Parameter
Values (Range)
Threshold voltage
16...176
Input osc. level
2...50
Input osc. hyst
2...50
3.1.6

Binary signals in card location Xnnn

Table 10: Binary input signals in card location Xnnn
Name
1
Xnnn-Input m
1
Authorization override is disabled, communication tools ask password to enter the merging unit.
2
Authorization override is enabled, communication tools do not need password to enter the
merging unit, except for WHMI which always requires it.
1
Xnnn = Slot ID, for example, X100, X110, as applicable
SMU615
Technical Manual
Values (Range)
1
0=False
2
1=True
Unit
Vdc
events/s
events/s
Adjust the binary input threshold voltage correctly. The threshold voltage
should be comparable to the nominal value instead of the default
minimum value. The factory default is 16 V to ensure the binary inputs'
operation regardless of the auxiliary voltage used (24, 48, 60, 110, 125,
220 or 250 V DC). However, the default value is not optimal for the
higher auxiliary voltages. The binary input threshold voltage should be
set as high as possible to prevent any inadvertent activation of the binary
inputs due to possible external disturbances. At the same time, the
threshold should be set so that the correct operation is not jeopardized
in case of undervoltage of the auxiliary voltage.
Type
BOOLEAN
Unit
Step
Default
1=True
0
0
0
0
0
0
0
0
Step
2
1
1
Basic functions
Description
Disable authority
Set password
Set password
Set password
Set password
Set password
Set password
Set password
Set password
Default
Description
16
Binary input
threshold voltage
30
Binary input oscil-
lation suppression
threshold
10
Binary input oscil-
lation suppression
hysteresis
Description
See the application manual for standard
configuration specific terminal connec-
tions
35

Advertisement

Table of Contents
loading

Table of Contents