ABB RELION SMU615 Technical Manual page 93

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

1MRS758407 C
F_TRIG Output signal
Table 97: F_TRIG Output signal
Name
Q
Settings
The function does not have any parameters available in PCM600.
3.13.1.9
T_POS_XX function blocks
Function block
Figure 54: Function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is
fed to the POS input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status
information. Respectively, T_POS_OK is used to validate the intermediate or faulty
breaker position.
Table 98: Cross reference between circuit breaker position and the output of the
function block
Circuit breaker
position
Intermediate '00'
Close '01'
Open '10'
Faulty '11'
Signals
T_POS_CL Input signals
Table 99: T_POS_CL Input signals
Name
POS
SMU615
Technical Manual
Type
BOOLEAN
Output of the function block
T_POS_CL
T_POS_OP
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
TRUE
Type
Default
Double binary
0
Basic functions
Description
Output signal
T_POS_OK
FALSE
TRUE
TRUE
FALSE
Description
Input signal
93