ABB RELION SMU615 Technical Manual page 59

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

1MRS758407 C
Current (Rogowski) sensor setting example
In this example, an 80 A/0.150 V at 50 Hz (0.180 V at 60 Hz) sensor, such as
the example shown in
application has a 150 A nominal current (In) corresponding to the protected
object's nominal current. The application nominal current is set to Rogowski
sensor setting
example sensor can be used with up to 4000 A application nominal current.
As the Rogowski sensor is linear and does not saturate, the 80 A/0.150 V at
50 Hz sensor also works as a 150 A/0.28125 V at 50 Hz sensor. When defining
another primary value for the sensor, also the nominal voltage has to be
redefined to maintain the same transformation ratio. However, the setting
in the protection relay (
which makes the same setting
60 Hz nominal frequency.
RSV
RSV
I
n
I
pr
f
n
K
r
In this example, the value is as calculated using the equation.
150
80
With this information, the protection relay's current (Rogowski) sensor
settings can be set.
Table 34: Example setting values for current (Rogowski) sensor
Setting
Primary current
Rated secondary value
When considering setting values for current sensor interfaces and for
protection functions utilizing these measurements, it should be noted
that the sensor measurement inputs in the relay have limits for linear
behavior. When this limit is exceeded, the input starts to saturate. The
saturation is reflected to the protection functions connected to the
sensor inputs. To ensure that the related protection functions operate
correctly, the start value setting for protection functions utilizing either
instantaneous or definite minimum time characteristics must not exceed
SMU615
Technical Manual
Figure 21
Primary current . Taken from the sensor's technical data, this
Rated Secondary Value ) is not in V but in mV/Hz,
I
n
K
×
r
I
pr
=
f
n
Rated Secondary Value in mV/Hz
Application nominal current
Sensor-rated primary current
Network nominal frequency
Sensor-rated voltage at the rated current in mV
A
150
mV
×
mV
A
= .
5 625
50
Hz
Hz
, is used in a 50 Hz electrical network. The
Rated Secondary Value valid for both 50 and
Value
150 A
5.625 mV/Hz
Basic functions
(Equation 1)
(Equation 2)
59