1MRS758407 C
5.4
Arc detection ARCDSARC
5.4.1
Identification
Function description
Arc detection
5.4.2
Function block
Figure 104: Function block
5.4.3
Functionality
The arc function ARCDSARC is used for detection of arc situations in air
insulated metal-clad switchgears caused by, for example, human errors during
maintenance or insulation breakdown during operation. The function monitors the
light information from an arc and delivers a signal, if the arc is detected.
The function contains a blocking functionality. Blocking deactivates all outputs and
resets timer.
5.4.4
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off". The operation counters are
cleared when
The operation of ARCDSARC can be described with a module diagram.
Figure 105: Functional module diagram
The functions receives the arc light information from the sensors. Input FLT_ARC
activates the drop-off timer. Once activated, the timer remains active until the input
SMU615
Technical Manual
IEC 61850
identification
ARCDSARC
Operation is set to "Off".
Supervision functions
IEC 60617
ANSI/IEEE C37.2
identification
device number
ARCD
AFD
Operation setting. The
161