1MRS758407 C
3.12.2.2
Functionality
The QTY_BAD function block evaluates the quality bits of the input signal and
passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined) signal
has quality which can be evaluated.
The OUT output indicates quality bad of the input signal. Input signals that have any
other than test bit set, will indicate quality bad status.
3.12.2.3
Signals
QTY_BAD Input signals
Table 55: QTY_BAD Input signals
Name
IN
QTY_BAD Output signals
Table 56: QTY_BAD Output signals
Name
OUT
3.12.3

QTY_GOOSE_COMM function block

3.12.3.1
Function block
Figure 39: Function block
3.12.3.2
Functionality
The QTY_GOOSE_COMM function block evaluates the peer device communication
status from the quality bits of the input signal and passes it as a Boolean signal to
the application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block.
When the output is in the true (1) state, the GOOSE communication is active. The
value false (0) indicates communication timeout.
SMU615
Technical Manual
Type
Default
Any
0
Type
BOOLEAN
Basic functions
Description
Input signal
Description
Output signal
77