Authorization Settings - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Basic functions
Table 7: Analog input settings, phase voltages
Parameter
Values (Range)
Primary voltage
0.100 ... 440.000
Secondary voltage
60...210
VT connection
1=Wye
2=Delta
Amplitude Corr A
0.9000 ... 1.1000
Amplitude Corr B
0.9000 ... 1.1000
Amplitude Corr C
0.9000 ... 1.1000
Division ratio
1000 ... 20000
Voltage input type
1=Voltage trafo
3=CVD sensor
Angle Corr A
-8.000 ... 8.000 deg deg
Angle Corr B
-8.000 ... 8.000 deg deg
Angle Corr C
-8.000 ... 8.000 deg deg
3.1.4

Authorization settings

Table 8: Authorization settings
Parameter
Remote Update
Secure Communication
Authority logging
Table continues on the next page
34
Unit
kV
V
Values (Range)
0=Disable
1=Enable
0=False
1=True
1=None
2=Configuration change
5=Settings edit
6=All
Step
0.001
1
0.0001
0.0001
0.0001
1
0.0001
0.0001
0.0001
Unit
Step
Default
0=Disable
1=True
1=None
1MRS758407 C
Default
Description
20.000
Primary rated volt-
age
100
Secondary rated
voltage
2=Delta
Voltage transducer
measurement con-
nection
1.0000
Phase A Voltage
phasor magnitude
correction of an
external voltage
transformer
1.0000
Phase B Voltage
phasor magnitude
correction of an
external voltage
transformer
1.0000
Phase C Voltage
phasor magnitude
correction of an
external voltage
transformer
10000
Voltage sensor divi-
sion ratio
1=Voltage trafo
Type of the voltage
input
0.0000
Phase A Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
0.0000
Phase B Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
0.0000
Phase C Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Description
Remote update
Secure Communication
Authority logging level
Technical Manual
SMU615