Basic functions
IEC 61850
station
Figure 77: Station authority is "L,S,S+R,L+S,L+S+R"
When station authority level "L,S,S+R,L+S,L+S+R" is used, control access can
be selected using the CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input CTRL_STA are applicable for
this station authority level.
"Station" and "Local + Station" control access can be reserved by using
the CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
Table 149: Station authority level "L,S,S+R,L+S,L+S+R" using CONTROL function block
L/R Control
Control FB
CTRL.LLN0.LocS
1
input
ta
CTRL_OFF
FALSE
CTRL_LOC
FALSE
CTRL_STA
FALSE
4
CTRL_REM
TRUE
CTRL_REM
FALSE
CTRL_ALL
FALSE
4
CTRL_ALL
TRUE
3.13.8.8
Signals
CONTROL input signals
Table 150: CONTROL input signals
Name
CTRL_OFF
CTRL_LOC
Table continues on the next page
1
Station client reserves the control operating by writing controllable point LocSta.
2
Client IEC 61850 command originator category is remote.
3
Client IEC 61850 command originator category is station.
4
CTRL_STA unconnected in application configuration. Station client reserves the control operating
by writing controllable point LocSta.
116
LOCAL
STATION
IEC 61850
IEC 61850
remote
remote
IEC 61850
station
IED
IED
L/R Control status
CTRL.LLN0.MltL
ev
FALSE
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
Type
BOOLEAN
BOOLEAN
S+R
L+S
IEC 61850
IEC 61850
remote
remote
IEC 61850
IEC 61850
station
station
IED
IED
Control access
L/R state
Local user
CTRL.LLN0.Loc
KeyHMI
0
1
3
3
7
6
5
Default
0
0
L+S+R
OFF
IEC 61850
IEC 61850
remote
remote
IEC 61850
IEC 61850
station
station
IED
IED
IEC 61850 client
2
x
x
x
x
x
Description
Control input OFF
Control input Local
Technical Manual
1MRS758407 C
IEC 61850 client
3
x
x
x
x
x
SMU615