Settings - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Condition monitoring functions
Name
IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INVALIDPOS
CLOSEPOS
6.1.7

Settings

6.1.7.1
SSCBR Non group settings
Table 198: SSCBR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Acc stop current
5.00...500.00
Open alarm time
0...200
Close alarm time
0...200
Spring charge time
0...60000
Alarm Op number
0...99999
Lockout Op num-
0...99999
ber
Current exponent
0.00...2.00
Difference Cor time -10...10
Alm Acc currents
0.00...20000.00
Pwr
LO Acc currents
0.00...20000.00
Pwr
Table continues on the next page
178
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
A
0.01
ms
1
ms
1
ms
10
1
1
0.01
ms
1
0.01
0.01
1MRS758407 C
Description
Accumulated currents power
(Iyt),exceeded lockout limit
Remaining life of CB excee-
ded alarm limit
CB 'not operated for long
time' alarm
Pressure below alarm level
Pressure below lockout level
CB is in open position
CB is in invalid position (not
positively open or closed)
CB is in closed position
Default
Description
1=on
Operation Off / On
10.00
RMS current set-
ting below which
engy acm stops
40
Alarm level setting
for open travel time
in ms
40
Alarm level Setting
for close travel time
in ms
15000
Setting of alarm
for spring charging
time of CB in ms
200
Alarm limit for
number of opera-
tions
300
Lock out limit for
number of opera-
tions
2.00
Current exponent
setting for energy
calculation
5
Corr. factor for
time dif in aux. and
main contacts open
time
2500.00
Setting of alarm
level for accumula-
ted currents power
2500.00
Lockout limit set-
ting for accumula-
ted currents power
Technical Manual
SMU615