Table 123: TPSGAPC Technical revision history
Technical revision
B
C
3.13.2.3
Minimum pulse timer TPMGAPC
Function block
Figure 63: Function block
Functionality
The Minimum minute pulse timer function TPMGAPC contains two independent
timers. The function has a settable pulse length (in minutes). The timers are used
for setting the minimum pulse length for example, the signal outputs. Once the
input is activated, the output is set for a specific duration using the
setting. Both timers use the same setting parameter.
Figure 64: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
TPMGAPC Input signals
Table 124: TPMGAPC Input signals
Name
IN1
IN2
SMU615
Technical Manual
Change
Outputs now visible in menu
Internal improvement
Type
Default
BOOLEAN
0=False
BOOLEAN
0=False
Basic functions
Pulse time
Description
Input 1
Input 2