T_Tcmd Function Block - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Basic functions
3.12.6.1
Function block
Figure 42: Function block
3.12.6.2
Functionality
The T_DIR function evaluates enumerated data of the FAULT_DIR data attribute of
the directional functions. T_DIR can only be used with GOOSE.
The DIR input can be connected to the GOOSERCV_ENUM function block, which
is receiving the LD0.<function>.Str.dirGeneral or LD0.<function>.Dir.dirGeneral data
attribute sent by another device.
In case the GOOSERCV_ENUM function block does not receive the value from the
sending device or it is invalid, the default value (0) is used in function outputs.
The outputs FWD and REV are extracted from the enumerated input value.
3.12.6.3
Signals
T_DIR Input signals
Table 63: T_DIR Input signals
Name
DIR
T_DIR Output signals
Table 64: T_DIR Output signals
Name
FWD
REV
3.12.7

T_TCMD function block

3.12.7.1
Function block
Figure 43: Function block
80
Type
Default
Enum
0
Type
Default
BOOLEAN
0
BOOLEAN
0
1MRS758407 C
Description
Input signal
Description
Direction forward
Direction backward
SMU615
Technical Manual