Settings - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Control functions
8.1.6.5
ESXSWI Output signals
Table 261: ESXSWI Output signals
Name
SELECTED
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
8.1.7

Settings

8.1.7.1
CBXCBR Non group settings
Table 262: CBXCBR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Select timeout
10000...300000
Pulse length
10...60000
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
Operation timeout
10...60000
Identification
Table 263: CBXCBR Non group settings (Advanced)
Parameter
Values (Range)
Operation counter
0...10000
Adaptive pulse
0=False
1=True
Table continues on the next page
238
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
ms
10000
ms
1
ms
1
Unit
Step
1
1MRS758407 C
Description
Object selected
Executes the command for
open direction
Executes the command for
close direction
Apparatus open position
Apparatus closed position
Apparatus position is ok
Opening is enabled based on
the input status
Closing is enabled based on
the input status
Default
Description
1=on
Operation mode
on/off
30000
Select timeout in
ms
200
Open and close
pulse length
4=sbo-with-en-
Select control mod-
hanced-security
el
500
Timeout for nega-
tive termination
CBXCBR1 switch
Control Object
position
identification
Default
Description
0
Breaker operation
cycles
1=True
Stop in right posi-
tion
Technical Manual
SMU615