1MRS758407 C
Parameter
Values (Range)
Directional Coef
-3.00...-0.50
Initial CB Rmn life
0...99999
Rated Op current
100.00...5000.00
Rated fault current
500.00...75000.00
Op number rated
1...99999
Op number fault
1...10000
Inactive Alm days
0...9999
Travel time Clc
1=From Cmd to Pos
mode
2=From Pos to Pos
Table 199: SSCBR Non group settings (Advanced)
Parameter
Values (Range)
Opening time Cor
-100...100
Closing time Cor
-100...100
Counter initial Val
0...99999
Ini Acc currents Pwr 0.00...20000.00
Life alarm level
0...99999
Pressure alarm
0...60000
time
Pres lockout time
0...60000
Ini inactive days
0...9999
Inactive Alm hours
0...23
6.1.8

Monitored data

SMU615
Technical Manual
Unit
Step
0.01
1
A
0.01
A
0.01
1
1
1
Unit
Step
ms
1
ms
1
1
0.01
1
ms
1
ms
10
1
h
1
Condition monitoring functions
Default
Description
-1.50
Directional coeffi-
cient for CB life cal-
culation
5000
Initial value for the
CB remaining life
1000.00
Rated operating
current of the
breaker
5000.00
Rated fault current
of the breaker
10000
Number of opera-
tions possible at
rated current
1000
Number of opera-
tions possible at
rated fault current
2000
Alarm limit value of
the inactive days
counter
2=From Pos to Pos
Travel time calcu-
lation mode selec-
tion
Default
Description
10
Correction factor
for open travel time
in ms
10
Correction factor
for CB close travel
time in ms
0
The operation num-
bers counter initial-
ization value
0.00
Initial value for ac-
cumulation energy
(Iyt)
500
Alarm level for CB
remaining life
10
Time delay for gas
pressure alarm in
ms
10
Time delay for gas
pressure lockout in
ms
0
Initial value of the
inactive days coun-
ter
0
Alarm time of the
inactive days coun-
ter in hours
179