Goosercv_Enum Function Block - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Basic functions
3.11.4.2
Functionality
The GOOSERCV_INTL function is used to connect the GOOSE double binary input to
the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.
3.11.4.3
Signals
GOOSERCV_INTL Output signals
Table 50: GOOSERCV_INTL Output signals
Name
POS_OP
POS_CL
POS_OK
VALID
3.11.5

GOOSERCV_ENUM function block

3.11.5.1
Function block
Figure 35: Function block
3.11.5.2
Functionality
The GOOSERCV_ENUM function block is used to connect GOOSE enumerator inputs
to the application.
3.11.5.3
Signals
74
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1MRS758407 C
Description
Position open output signal
Position closed output signal
Position OK output signal
Output signal
SMU615
Technical Manual