Basic functions
Fault indication
Fault
code
Internal Fault File
7
system error
Internal Fault Test
8
Internal Fault SW
10
watchdog error
Internal Fault SO-
43
relay(s),X100
Internal Fault SO-
44
relay(s),X110
Internal Fault SO-
45
relay(s),X120
Internal Fault SO-
46
relay(s),X130
Internal Fault PO-
53
relay(s),X100
Internal Fault PO-
54
relay(s),X110
Internal Fault PO-
55
relay(s),X120
Internal Fault PO-
56
relay(s),X130
Internal Fault Light
59
sensor error
Table continues on the next page
40
Additional
Fast self-
information
recovery
attempt
(# of
attempts)
Start up error or
Yes (2)
runtime error: file
system error
Internal fault test
No
activated manual-
ly by the user.
Start up error:
No
Watchdog reset
has occurred too
many times with-
in an hour. Note!
This is different
indication than
Warning code 10:
Watchdog reset
Runtime error:
Yes (2)
Faulty Signal Out-
put relay(s) in card
located in slot
X100.
Runtime error:
Yes (2)
Faulty Signal Out-
put relay(s) in
card located in
slot X110.Runtime
error:
Runtime error:
Yes (2)
Faulty Signal Out-
put relay(s) in card
located in slot
X120.
Runtime error:
Yes (2)
Faulty Signal Out-
put relay(s) in card
located in slot
X130.
Runtime error:
Yes (2)
Faulty Power Out-
put relay(s) in card
located in slot
X100.
Runtime error:
Yes (2)
Faulty Power Out-
put relay(s) in card
located in slot
X110.
Runtime error:
Yes (2)
Faulty Power Out-
put relay(s) in card
located in slot
X120.
Runtime error:
Yes (2)
Faulty Power Out-
put relay(s) in card
located in slot
X130.
Runtime error:
Yes (2)
Faulty ARC light
sensor input(s).
Slow 10
Immediate
Action in permanent fault state
min self-
permanen
recovery (#
t IRF-
of
mode
attempts)
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restart-
ing, replace the relay, most probably
hardware failure in CPU module.
No
-
Just check the "Internal fault test"
-setting parameter position, if relay
is in test mode
No
Yes
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restarting,
replace the relay.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X100.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X110.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X120.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X130.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X100.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X110.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X120.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, exchange the hard-
ware module in slot X130.
Yes (3)
No
Check wirings. Restart the relay. If
recovered by restarting, continue
1MRS758407 C
SMU615
Technical Manual